Application of automatic load transfer on feeder utilisation balance

Bai, X.; Strickland, D. and Harrap, C. (2015). Application of automatic load transfer on feeder utilisation balance. IN: IET International Conference on Resilience of Transmission and Distribution Networks (RTDN) 2015. IET Conference Publications . IET.

Abstract

This paper looks at how automatic load transfer may be used as a possible planning tool to help deliver faster connections for customers. A trial on an area of overhead line Network is presented to show how improvements in % feeder utilisation may be realised by changing the location of the open point. The reported Network data is compared to calculated data under two different configurations over a two week trial period. The results show that ALT open point determination in the presence of generation is different from a load only circuit and that the open points may not be fixed with time. Looking at improvements in Network headroom may not be conducive to other improvements in the network such as loss reduction or improving voltage profiles.

Publication DOI: https://doi.org/10.1049/cp.2015.0886
Divisions: Engineering & Applied Sciences > Electrical, electronic & power engineering
Event Title: IET International Conference on Resilience of Transmission and Distribution Networks
Event Type: Other
Event Dates: 2015-09-22 - 2015-09-24
Uncontrolled Keywords: automatic load transfer,feeder utilisation balance,network capacity,network re-configuration,Electrical and Electronic Engineering